[ONGOING] MITTO'S INCIDENT NOTIFICATION

Major
August 15, 2026 - Started 6 days ago
Official incident page

Incident Report

Service Impact: *Outage ongoing in Data Center*. Start: 2026-08-15 05:10 CEST End: Ongoing Description: Cooling system failure due to a leak in the chilled water system. Service Status There is customer impact. Temperatures are affected, with the highest now at 50 degrees Celsius. The leak has been closed up and chiller water is refilling. Customers in the affected data halls are advised to review their business continuity plans. Mitigation & Planned Actions Mitigation & Planned Actions • Issue investigation — Completed • Leak closure — Completed • Chiller water refilling — In Progress Suspected Initial Cause The suspected initial cause is a cooling system failure due to a leak in the cold water system. Incident Summary Equinix IBX Site Staff reports that on 07-JUN-2024 at 14:30 Site Local Time, a pipe from the Computer Room Air Handler (CRAH) unit was leaking, affecting all cooling systems in the facility. The leak has since been closed up and chiller water refilling is underway. Customer impact: Customers may experience service degradation, intermittent connectivity, or a complete inability to access hosted services and applications. Updates will be provided as soon as further information becomes available. Thank you for understanding.

Trusted by 1,000+ teams

The Status Page Aggregator with Early Outage Detection

Stop finding out about outages from your users. Monitor 6,320+ cloud services and get alerted the second something breaks.

IsDown status aggregator dashboard
Latest Updates ( sorted recent to last )
MONITORING 5 days ago - at 08/16/2026 08:09AM

We have not seen any active issues up to this point, all systems are fully operational. Our team will continue to monitor all services closely.

MONITORING 5 days ago - at 08/16/2026 07:05AM

We are continuing to monitor for any further issues.

MONITORING 5 days ago - at 08/15/2026 07:19PM

Service Restoration Update - 15 Aug 2026 – 21:11 CEST

Service has been tentatively restored at our Equinix datacentre, and message delivery is now resuming. Our teams continue to monitor the environment closely and are working through the remaining message backlog.
We will provide further updates as stability is confirmed.

We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 5 days ago - at 08/15/2026 06:34PM

Service Restoration Update - 15 Aug 2026 – 20:29 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — Completed
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chillers 7, 8, and 9 Restoration — Completed
• Additional chiller vendors en route — Completed
• Restoration of cooling to the affected areas of second floor (Module 215) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 5 days ago - at 08/15/2026 06:09PM

Service Restoration Update - 15 Aug 2026 – 20:02 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — Completed
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chillers 7, 8, and 9 Restoration — Completed
• Additional chiller vendors en route — Completed
• Restoration of cooling to the affected areas of second floor (Module 215) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 5 days ago - at 08/15/2026 05:59PM

Service Restoration Update - 15 Aug 2026 – 19:35 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — Completed
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chillers 7, 8, and 9 Restoration — Completed
• Additional chiller vendors en route — Completed
• Restoration of cooling to the affected areas of second floor (Module 215) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 5 days ago - at 08/15/2026 05:11PM

Service Restoration Update - 15 Aug 2026 – 19:05 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — Completed
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chillers 7, 8, and 9 Restoration — Completed
• Additional chiller vendors en route — Completed
• Restoration of cooling to the affected areas of second floor (Module 215) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 5 days ago - at 08/15/2026 04:48PM

Service Restoration Update - 15 Aug 2026 – 18:39 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — Completed
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chillers 7, 8, and 9 Restoration — Completed
• Additional chiller vendors en route — Completed
• Restoration of cooling to the affected areas of second floor (Module 215) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 5 days ago - at 08/15/2026 04:09PM

Service Restoration Update - 15 Aug 2026 – 18:06 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress
• Additional chiller vendors en route - Completed

The suspected initial cause is a cooling system failure due to a leak in the chilled water system.
We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 5 days ago - at 08/15/2026 03:40PM

Service Restoration Update - 15 Aug 2026 – 17:39 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress
• Additional chiller vendors en route - Completed

The suspected initial cause is a cooling system failure due to a leak in the chilled water system.
We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 5 days ago - at 08/15/2026 03:11PM

Service Restoration Update - 15 Aug 2026 – 17:09 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress
• Additional chiller vendors en route - In Progress

The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 5 days ago - at 08/15/2026 02:46PM

Service Restoration Update - 15 Aug 2026 - 16:31 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress
• Additional chiller vendors en route - In Progress

The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 5 days ago - at 08/15/2026 02:44PM

Service Restoration Update - 15 Aug 2026 - 16:04 CEST
Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress

The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 5 days ago - at 08/15/2026 01:41PM

Service Restoration Update - 2026-08-15 15:42 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 6 days ago - at 08/15/2026 01:17PM

Service Restoration Update - 2026-08-15 15:17 CEST

Mitigation & Planned Actions
• First leak closure — Isolated
• Second leak closure — Isolated and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 6 days ago - at 08/15/2026 12:54PM

Service Restoration Update - 2026-08-15 14:53 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 6 days ago - at 08/15/2026 12:20PM

Service Restoration Update - 2026-08-15 14:20 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 6 days ago - at 08/15/2026 11:53AM

Service Restoration Update - 2026-08-15 13:53 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 6 days ago - at 08/15/2026 11:24AM

Service Restoration Update - 2026-08-15 13:24 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — Planned
Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 6 days ago - at 08/15/2026 10:56AM

Service Restoration Update - 2026-08-15 12:57 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chiller water refilling — In Progress
• Second chiller water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — In Progress
• Chiller test run (one chiller at a time) — Planned
Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 6 days ago - at 08/15/2026 10:25AM

Service Restoration Update - 2026-08-15 12:26 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chiller water refilling — In Progress
• Second chiller water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Chiller test run (one chiller at a time) — Planned

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.
We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 6 days ago - at 08/15/2026 09:56AM

Service Restoration Update - 2026-08-15 11:55 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chiller water refilling — In Progress
• Second chiller water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Chiller test run (one chiller at a time) — Planned

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.
We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 6 days ago - at 08/15/2026 09:29AM

Service Restoration Update - 2026-08-15 11:28 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chiller water refilling — In Progress
• Second chiller water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Chiller test run (one chiller at a time) — Planned

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.
We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 6 days ago - at 08/15/2026 09:03AM

Service Restoration Update - 2026-08-15 11:02 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chiller water refilling — In Progress
• Second chiller water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Chiller test run (one chiller at a time) — Planned

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.
We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 6 days ago - at 08/15/2026 08:31AM

Service Restoration Update - 2026-08-15 10:30 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Verifying
• Chiller water refilling — In Progress (nearly complete)
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Onsite, Restoration In Progress
• Fire system vendor to restore fire system — Onsite, Restoration In Progress
• Elevator restoration — Completed
• Chiller test run (one chiller at a time) — In Progress

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 6 days ago - at 08/15/2026 08:04AM

Service Restoration Update - 2026-08-15 10:01 CEST

Mitigation & Planned Actions (Mitto DR Activation in progress)
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress (nearly complete)
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress (nearly complete)
• Chiller vendor engagement — Enroute to the site
• Fire system vendor to restore fire system — Arrived on-site, Restoration In Progress
• Elevator restoration — Completed
• Chiller test run (one chiller at a time) — In Progress

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted for approximately three hours, and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 6 days ago - at 08/15/2026 07:47AM

Service Restoration Update - 2026-08-15 09:33 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress (nearly complete)
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Enroute to the site (ETA 09:30 Site Local Time)
• Fire system vendor to restore fire system — Enroute to the site (ETA 09:30 Site Local Time)
• Elevator restoration — Completed
• Pump operation to purge air from system — Planned
• Chiller test run (one chiller at a time) — Planned

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted for approximately three hours, and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

IDENTIFIED 6 days ago - at 08/15/2026 07:06AM

Service Restoration Update - 2026-08-15 08:58 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Enroute to the site (ETA 09:30 Site Local Time)
• Fire system vendor to restore fire system — Enroute to the site (ETA 09:30 Site Local Time)
• Elevator restoration — Completed

IDENTIFIED 6 days ago - at 08/15/2026 06:39AM

Service Restoration Update - 2026-08-15 08:31 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Vendor engagement — Enroute to the site (ETA 20 minutes)
• Fire system vendor to restore fire system — In Progress
• Elevator unavailable— In Progress

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted for approximately three hours, and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.

IDENTIFIED 6 days ago - at 08/15/2026 06:37AM

Service Restoration Update - 2026-08-15 07:57 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress
• Additional hose installation to accelerate refilling process — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Vendor engagement — Enroute to the site (ETA 20 minutes)
• Fire protection vendor activation — Enroute to the site

IDENTIFIED 6 days ago - at 08/15/2026 06:36AM

Service Restoration Update - 2026-08-15 07:29 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress
• Additional hose installation to accelerate refilling process — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Vendor engagement — In Progress (ETA 20 minutes)
• Fire protection vendor activation — Enroute to the site

IDENTIFIED 6 days ago - at 08/15/2026 06:35AM

Service Restoration Update - 2026-08-15 06:58 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress
• Additional hose installation to accelerate refilling process — In Progress
• Mobile dehumidifier deployment — Completed
• Water clearing from affected areas — In Progress
• Vendor engagement — In Progress (ETA one hour)

IDENTIFIED 6 days ago - at 08/15/2026 06:34AM

Service Restoration Update - 2026-08-15 06:32 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress
• Mobile dehumidifier deployment — Completed
• Water clearing from affected areas — In Progress
• Vendor engagement — In Progress (ETA one hour)

IDENTIFIED 6 days ago - at 08/15/2026 06:25AM

Service Restoration Update - 2026-08-15 06:32 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress
• Mobile dehumidifier deployment — Completed
• Water clearing from affected areas — In Progress
• Vendor engagement — In Progress (ETA one hour)

INVESTIGATING 6 days ago - at 08/15/2026 04:10AM

Service Impact: *Outage ongoing in Data Center*.
Start: 2026-08-15 05:10 CEST
End: Ongoing

Description:

Cooling system failure due to a leak in the chilled water system.

Service Status

There is customer impact. Temperatures are affected, with the highest now at 50 degrees Celsius. The leak has been closed up and chiller water is refilling. Customers in the affected data halls are advised to review their business continuity plans.

Mitigation & Planned Actions

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress

Suspected Initial Cause

The suspected initial cause is a cooling system failure due to a leak in the cold water system.

Incident Summary

Equinix IBX Site Staff reports that on 07-JUN-2024 at 14:30 Site Local Time, a pipe from the Computer Room Air Handler (CRAH) unit was leaking, affecting all cooling systems in the facility. The leak has since been closed up and chiller water refilling is underway.

Customer impact:

Customers may experience service degradation, intermittent connectivity, or a complete inability to access hosted services and applications. Updates will be provided as soon as further information becomes available.

Thank you for understanding.